Round Downpipe Technical Information

As a general guide, in non cyclonic areas, for every 1m2 of roof area drained, 70mm2 of downpipe is required. This calculation is based on the assumption that the maximum rainfall does not exceed 125mm per hour.

It is considered the best practice to drain to different points, using smaller downpipes rather than to one large outlet. Where possible, downpipes should be spaced at not more than 12000mm centres.

For a more accurate guide, consult the Installation Code for Metal Roofing and Wall Cladding SAA HB39-1997.



Material Specification and Sizes
Profile BMT (mm) Tensile (MPa) Size (mm) Roof Area Drained (m²)
0.40 and 0.50 G300 50 30
65 45
75 65
90 90
100 115
125 170
150 250
175* 345
200* 450
225* 570
*1800mm lengths only